PAGE 6 20 NOV 2003 ADC970
Conversion of Real-World Inputs into Register Values
Selected Range
Input
mA or Volts
Data Out Conversion Factor
> +5.11 32767
+5.00 32000
0.00 0
-5.00 -32000
±5.00 V
< -5.11 -32768
0.00015625
> +10.23 32767
+10.00 32000
0.00 0
-10.00 -32000
±10.00 V
< -10.23 -32768
0.0003125
< +20.37 32767
+20.00 32000
+4.00 0
-12.00 -32000
4.20 mA
> -12.38 -32768
0.0005
> +20.47 32767
+20.00 32000
0 0
-20.00 -32000
±20.00 mA
< -20.47 -32768
0.0006250
Note: For the 4 to 20mA range, the offset, 4mA, must first be subtracted from the physical input value
before dividing by the scale factor to yield the expected %AQG value for the given input.
7 SETTING ID SWITCHES
CsCAN Network IDs are set using the hexadecimal number system from 01 to FD. The decimal
equivalent is 1-253. Refer to following Conversion Table, which shows the decimal equivalent of
hexadecimal numbers. Set a unique Network ID by inserting a small Phillips screwdriver into the two
identical switches.
Note: The CsCAN Baud Rate for SmartStix I/O is fixed at 125KBaud
Close-up of Switches
LO (x1)
HI (x16)
MS
NS
PWR
SmartStix I/O
006DIQ001
Use this switch to set
the Low Digit has an
x1 multiplier.
Use this switch to set the
High Digit has an x16
multiplier.
Power and Diagnostic
LEDs