CH. 3 MAN0890-02-EN
August 20, 2009 Page 18 of 96 ECN # 979
3.2. Mounting Orientation
NOTE:
There are NO orientation restrictions on the QX751. However, the above orientation provides for optimum
readability of the screen and ease of use of the keypad.
Figure 3.2Orientation of QX751
3.3 Factors Affecting Panel Layout Design and Clearances
The designer of a panel layout needs to assess the requirements of a particular system and to consider
the following design factors. A convenient checklist is provided on page
20.
a. Clearance / Adequate Space
Install devices to allow sufficient clearance to open and close the panel door.
Table 3.1 – Minimum Clearance Requirements for Panel Box and Door
Minimum Distance between base of device and sides of
cabinet
2 inches (50.80mm)
Minimum Distance between base of device and wiring ducts 1.5 inches (38.10mm)
If more than one device installed in panel box (or on door):
Minimum Distance between bases of each device
4 inches between bases of each
device (101.60mm)
When door is closed:
Minimum distance between device and closed door
(Be sure to allow enough depth for QX751/BP.)
2 inches (50.80mm)
Warning: It is important to follow the requirements of the panel manufacturer and to follow
applicable electrical codes and standards.
001OCS001