MAN0871-02 21 AUGUST 2007 PAGE 1
Specifications / Installation HE-XT103-10
1 Specifications
HE-XT103-10 Specifications
Digital DC Inputs XLT103-10
Digital DC
Outputs
XLT103-10
Inputs per Module
12 including 4 configurable
HSC inputs
Outputs per
Module
12 including 2 configurable
PWM outputs
Commons per
Module
1
Commons per
Module
1
Input Voltage
Range
12 VDC / 24 VDC Output Type Sourcing / 10 K Pull-Down
Absolute Max.
Voltage
35 VDC Max.
Absolute Max.
Voltage
28 VDC Max.
Input Impedance
10 kΩ
Output
Protection
Short Circuit
Input Current
Positive
Logic
Negative Logic
Max. Output
Current per
point
0.5 A
Upper Threshold 0.8 mA -1.6 mA
Max. Total
Current
4 A Continuous
Lower Threshold 0.3 mA -2.1 mA
Max. Output
Supply Voltage
30 VDC
Max Upper
Threshold
8 VDC
Minimum Output
Supply Voltage
10 VDC
Min Lower
Threshold
3 VDC
Max. Voltage
Drop at Rated
Current
0.25 VDC
OFF to ON
Response
1 ms
Max. Inrush
Current
650 mA per channel
ON to OFF
Response
1 ms Min. Load None
HSC Max.
Switching Rate
10 kHz Totalizer/Pulse,Edges
5 kHz Frequency/Pulse,Width
2.5 kHz Quadrature
OFF to ON
Response
1 ms
Thermistor
Inputs, Medium
Resolution
XLT103-10
ON to OFF
Response
1 ms
Number of
Channels
2
Output
Characteristics
Current Sourcing (Pos logic)
General Specifications
Input Ranges
Safe input voltage
range
Input Impedance
(Clamped @ -0.5
VDC to 12 VDC)
10K OHM
Thermistor
Half Bridge
9.59K ohm pulled up to
4.8 VDC
Required Power
(Steady State)
150 mA @ 24 VDC
Required Power
(Inrush)
30 A for 1 ms @ 24 VDC
Nominal Resolution
%AI at 10K Ohm
10 Bits
15,008 counts
Primary Power
Range
10 – 30 VDC
Conversion Speed
All channels converted once
per ladder scan
Relative Humidity
5 to 95% Non-
condensing
Max. Error at 25°C
reading / ambient
±0.5°F or ±0.3°C
Using specified linearization
in ladder program
Operating
Temperature
-10°C to +60°C
Terminal Type
Screw Type,5 mm
Removable
Additional error for
reading / ambient
temperatures other
than 25°C
TBD
CE
UL
See Compliance Table at
http://www.heapg.com/Support/compliance.htm
Filtering
160 Hz hash (noise) filter
1-128 scan digital running
average filter
Weight 12.5 oz. (354.36 g)
Clock Accuracy +/- One Minute/Month at 20C
2 Panel Cut-Out and Dimensions
Note: Max. panel thickness: 5 mm.
3 Ports / Connectors / Cables
Note: The case of the XLE is black, but for clarity, it is shown in a
lighter gray color.
Want More Information?
To download the XLE User
Manual (MAN0863), refer
to Technical Support in this
document.
3.622 [92mm]
3.622 [92mm]
001XLE002
Refer to XLT User
Manual (MAN0863) for
panel box information
and a handy checklist of
requirements.
Note:
The tolerance to meet
NEMA standards is
± 0.005” (0.1 mm).
To Remove Back Cover:
Unscrew 4 screws located on
the back of the unit.
Lift lid.
CAUTION: Do not over tighten
screws when screwing the lid
back on.
001ACC009
Power Connector
Power Up:
Connect to Earth Ground.
pply 10 – 30 VDC.
Screen lights up.
CAN Connector
Use the CAN Connector
when using CsCAN network.
I/O Jumpers (Not Shown): I/O Jumpers (JP) are located
internally. To access, remove back cover of unit.
Wiring Connectors (J1 – J4), I/O Jumpers (JP1-3), and DIP
Switches (RS-485) are described in the DIP Switches, Wiring
and Jumpers section of this document.
XLT OCS Model: HE-
T103-10
12 Digital DC Inputs / 12 Digital Outputs
2 10K Thermistor Inputs
MJ1
(RS-232 / RS-485)
MJ2
(RS-232 / RS-485)
J1
I/O
Jumper
Memory Slot
001XLE029-R2
J2
I/O
Jumper
NET 1
(CsCAN)
Power
DIP
Switch
Note: The highest usable frequency is 65 KHz for the PWM output
Comentarios a estos manuales