Getting Started MAN0575-04-EN
PAGE 15 of 97
© Horner APG.This drawing is the property of Horner APG. And shall not be disclosed or reproduced except as specifically authorised.
Profibus Modules User Manual
EO 09-0009
3.3 Configuration of a SmartStack Profibus DP Master to any Profibus DP Slave
The following describes the steps to configure a SmartStack Profibus DP Master to any Profibus DP
Slave:
Action Menu in the System Configurator
Create a new project
File > New > PROFIBUS
Copy GSD file of the DP Slave, if the Slave is not in the
selection list. Horner module GSD’s loaded by default.
File > Copy GSD
Choose Horner DP Master and provide bus address
Insert > Master
Choose DP Slave and provide bus address
Insert > Slave
Assign the input and output modules (*1)
Mark the Slave (left Mouse click), then
Settings > Slave Configuration
Assign the offset addresses
Assign the DP Slave Parameter data, if the Slave needs
Parameter data
Mark the Slave (left Mouse click), then
Settings > Parameter Data
Set the bus parameter Mark the Master (left Mouse click), then
Settings > Bus Parameters
Set device assignment if no automatic assignment has
occurred
Mark the Master (left Mouse click), then
Settings > Device Assignment
Save project
File > Save
Download to the Master. Mark the Master (left Mouse click), then
Online > Download
Download to the Slave (if a Horner DP Slave). Mark the Slave (left Mouse click), then
Online > Download
Live List Mark the Master (left Mouse click), then
Online > Live List
Start Debugger Mark the Master (left Mouse click), then
Online > Start Debug Mode
Device diagnostic Mark the Slave (left Mouse click), then
Online > Device Diagnostic
Stop Debugger
Online > Stop Debug Mode
Global Diagnostic Mark the Master (left Mouse click), then
Online > Global State Field
Transfer user data:
Write output, read input
Mark the Master (left Mouse click), then
Online > I/O Monitor
Figure 3.2. Steps for Configuration of a SmartStack Profibus DP Master to any Profibus DP
Slave
Note (*1): The Offset addresses assigned in the Slave configuration are always related to the DP
Master.