CH.10 MAN0892-03-EN
February 25, 2010 Page 46 of 109 # 1039
Run = QX is in Run mode
Scan Rate(mS): 0.0 = QX is not in Run mode
0.1 to 999.9 = Average number of mS for each ladder scan
Lcl Net Use (%): 0.0 to 100.0 = CAN network bandwidth % used by this QX node
All Net Use (%): 0.0 to 100.0 = CAN network bandwidth % used by all nodes
Ladder Size: x = Number of bytes in application ladder program
Config Size: x = Number of bytes in application I/O configuration
Graphics Size: x = Number of bytes in application graphic screens
String Size: x = Number of bytes in application string table
Bitmap Size: x = Number of bytes in application bitmaps
Text Tbl Size: x = Number of bytes in application text tables
Font Tbl Size: x = Number of bytes in application font tables
Protocol Size: x = Number of bytes in application downloaded protocols
SMS Size: x = Number of bytes in application SMS configuration
Firmware Rev: xx.yy = Current firmware version
BIOS Rev: x.y = Current BIOS (Basic Input/Output System) version
FPGA Rev: x.y = Current FPGA (Field Programmable Gate Array)
version
Self-Test: Ok = All power-on self-tests passed
Fault = One or more power-on self-tests failed
View OCS Diags
The View OCS Diags Sub-Menu displays 11 System Diagnostics, none of which are editable. The first
two System Diagnostics are critical. If any of them indicate a Fault condition, the QX will not enter or
remain in Run mode, and the problem must be investigated and corrected.
Logic Error: Ok = All executed ladder instructions are legal for loaded
Firmware
Fault = A ladder instruction not supported by firmware was
Found
User Program: Ok = Ladder program and I/O configuration loaded
Successfully
Fault = Ladder program or I/O configuration not loaded or load
Failed
Following System Diagnostics are informational. If any of them indicate a Warning condition, the QX can
still enter and remain in Run mode, but the problem should be investigated and corrected.