Horner-apg QX351 OCS HEQX351C103 Manual de usuario Pagina 47

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 109
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 46
MAN0892-03-EN CH.10
February 25, 2010 Page 47 of 109 #1039
User Graphics: Ok = Application graphics objects loaded successfully
Warn = Application graphics objects not loaded or load failed
W-Dog Trips: 0 = Watchdog timer has not tripped since the last power-up
x = Number of times watchdog timer has tripped
Net Errors: 0 = No CAN network bus-off errors have occurred
x = Number of CAN network bus-off errors that have occurred
Network State: Ok = At least one other node was found on the CAN network
Warn = No other nodes were found on the CAN network
Network ID: Ok = This node’s CAN Network ID was in the range 1 to 253
Warn = This node’s CAN Network ID was out of range at power-up
Dup Net ID: Ok = This node’s Network ID is unique on the CAN network
Warn = This node’s Network ID is duplicated in another node
Clock Error: Ok = Time and date have been set
Warn = Time and date need to be set
I/O System: Ok = I/O configuration matches the installed I/O and COM
modules
Warn = I/O configuration needs updating to match installed
Modules
Battery: Ok = Battery voltage level at an acceptable level
Warn = Battery voltage level below an acceptable level