Specifications / Installation
Specifications / Installation
7 Built-in I/O (Model 2, 3, 4 & 5)
Note: The Cscape Module Setup configuration must match the
selected I/O (JP) jumper settings.
(JP1 & JP2) and
wiring connectors
(J1 and J2) with back cover
removed.
Note: When using JP2 (A1-A4), each channel can be
independently configured.
Model 2 Jumper Setting Details
"WARNING: EXPOSURE TO SOME CHEMICALS MAY DEGRADE
THE SEALING PROPERTIES OF MATERIALS USED IN THE Tyco relay PCJ
Cover / case & base: Mitsubishi engineering Plastics Corp.
5010GN6-30 or 5010GN6-30 M8 (PBT)
Sealing Material: Kishimoto 4616-50K (I part epoxy resin)
It is recommended to periodically inspect the relay for any
degradation of properties and replace if degradation is found
The XL4 model 2 (HE-XC1E2) features 12 DC Inputs, 6 Relay outputs, and 4 Analog Inputs. The DC Inputs are 12/24Vdc
compatible, and can be jumpered for Positive Logic (sinking), or Negative Logic (sourcing). Four of the inputs (H1-H4) can
be used for high-speed functions up to 500kHz. The 12-bit Analog Inputs can be jumpered for voltage (0-10V) or current
(4-20mA) on a channel by channel basis. The Relay outputs are isolated, supporting AC and DC voltages, with output
currents of up to 3A/relay, 5A total.
JP1 Digital DC In / HSC
Positive Negative
Logic Logic
I1
I2
I3
I4
0V
A1
A2
0V
I5
I6
I7
I8
A3
A4
H1
001XLE017
12-24VDC
LOOP PWR
20mA
0-10VDC
JP2 Analog In (A1 – A4)
Current Voltage
(20 mA) (10 V)
001XLE015
0V ON J1
12-24VDC
R2
C2
R3
C3
R6
C6
R4
C4
R5
C5
R1
C1
H4
H2
H3
LOAD
230VAC
OR
25VDC
N
L
LOAD
230VAC
OR
25VDC
N
L
LOAD
230VAC
OR
25VDC
N
L
LOAD
230VAC
OR
25VDC
N
L
LOAD
230VAC
OR
25VDC
N
L
LOAD
230VAC
OR
25VDC
N
L
All XL4 models (except the HE-XCE0) feature built-in I/O. The I/O is mapped into OCS Register space, in three separate
areas – Digital/Analog I/O, High-Speed Counter I/O, and High-speed Output I/O. Digital/Analog I/O location is fixed starting
at 1, but the High-speed Counter and High-speed Output references may be mapped to any open register location. For
more details on using the High-Speed Counter and High-Speed Outputs, see the XL4 OCS User’s Manual (MAN0964).
Reserved areas maintain backward compatibility
with other XL Series OCS models
*Starting Address locations for %I, %Q, %AI & %AQ may
be re-mapped by user
PWM or Pulse-Train
Parameters
*Starting Address locations for %I & %AQ may be
remapped by user
**Q1-Q2 are part of the Fixed I/O Map. In High-Speed
Output mode they can be used to initiate a Stepper/PTO
Comentarios a estos manuales