MAN0855-01-EN Specifications / Installation
__________________________________________________________________________________________________________________________________________________
7/22/2009 Page 2 of 4 ECN # 956
5 Wiring and Jumpers
Wire according to the type of inputs / outputs used, and select the
appropriate jumper option.
5.1. Wiring Examples
J1 Orange
Terminal
Connector
XE102
Name
I1 IN1
I2 IN2
I3 IN3
I4 IN4
I5 IN5
I6 IN6
I7 IN7
I8 IN8
H1 HSC1 /IN9
0V Ground
A1 Thermistor 1
A2 Thermistor 2
A3 Thermistor 3
A4 Thermistor 4
0V Ground
J2 Black
Terminal
Connector
XE102
Name
C6 Relay 6 COM
R6 Relay 6 NO
C5 Relay 5 COM
R5 Relay 5 NO
C4 Relay 4 COM
R4 Relay 4 NO
C3 Relay 3 COM
R3 Relay 3 NO
C2 Relay 2 COM
R2 Relay 2 NO
C1 Relay 1 COM
R1 Relay 1 NO
H4 HSC4 / IN12
H3 HSC3 / IN11
H2 HSC2 / IN10
5.2 I/O Jumpers Settings (JP1)
5.3 External DIP Switch Settings (or Jumpers Settings)
6 Derating
J1
JP2
JP1
J2
001XLE025
Location of I/O jumpers (JP
)
and wiring connectors
(J1 and J2).
I1
0V
001XLE036
12-24VDC
I1
0V
Positive Logic In Negative Logic In
Positive Logic vs. Negative Logic Wiring
The XLe can be wired for Positive Logic inputs or
Negative Logic inputs.
Wiring Specifications
For I/O wiring (discrete), use the
following wire type or equivalent:
Belden 9918, 18 AWG (0.8 mm
2
)
or larger.
For shielded Analog I/O wiring,
use the following wire type or
equivalent: Belden 8441, 18
AWG (0.8 mm
2
) or larger.
For CAN wiring, use the
following wire type or equivalent:
Belden 3084, 24 AWG (0.2 mm
2
)
or larger.
Use copper conductors in field
wiring only, 60/75° C
Pin
MJ1 Pins MJ2 Pins
Signal Direction Signal Direction
8
TXD OUT TXD OUT
7
RXD IN RXD IN
6
0 V Ground 0 V Ground
5*
+5
60mA
OUT
+5
60mA
OUT
4
RTS OUT TX- OUT
3
CTS IN TX+ OUT
2
RX- /
TX-
IN / OUT RX- IN
1
RX+ /
TX+
IN / OUT RX+ IN
1
8
4 Serial Communications:
MJ1: (RS-232 / RS-485) Use for Cscape programming and
Application
-Defined Communications.
MJ2: (RS-232 / RS-485) Use for Application-Defined
Communications.
* +5 on XLe Rev E and later
Note:
The Cscape Module Setup configuration must match the
selected I/O (JP) jumper settings.
001XLE026
JP1 Digital DC In / HSC
Positive Negative
Logic Logic
Default
001XLE015
0V ON J1
12-24VDC
R2
C2
R3
C3
R6
C6
R4
C4
R5
C5
R1
C1
H4
H2
H3
LOAD
230VAC
OR
25VDC
N
L
LOAD
230VAC
OR
25VDC
N
L
LOAD
230VAC
OR
25VDC
N
L
LOAD
230VAC
OR
25VDC
N
L
LOAD
230VAC
OR
25VDC
N
L
LOAD
230VAC
OR
25VDC
N
L
XE102 J2 Black
Positive Logic
Digital In / Relay Out
Some XLes have jumpers to set
RS-
485 port termination, though
most use DIP Switches.
The External Jumpers or DIP
Switches are used for termination
of the RS-
485 ports. The XLE is
shipped un-terminated.
To terminate, select one of the
jumpers shipped with the product
and insert it based upon the option
that is desired or, select the switch
and configure based upon the
option that is desired.
Factory Use
(default – none)
MJ2 Termination
(default – none)
MJ1 Termination
(default – none)
001XLE037
As seen when looki
ng at the top of the XLE unit: Refer to
Section 4 for the location of the External Jumpers.
XLE102 Relay Life Expectancy
0
10
20
30
40
1 2 3 4
Contact Current (A)
Operation
(x10
4
)
001XLE037-R1
Factory Use
(default – none)
MJ2 Termination
(default – none)
MJ1 Termination
(default – none)
I1
I2
I3
I4
0V
A1
A2
0V
I5
I6
I7
I8
A3
A4
H1
001XLE067
12-24VDC
T
T
T
T
XE102 J1 Orange
Positive Logic In
Digital In /
Analog In