PAGE 2 21 August 2007 MAN0848-02
XLE103-10 Specifications / Installation
Section 3 continued
4 Wiring and Jumpers
Wire according to the type of inputs / outputs used and select the appropriate jumper
option.
4.1. I/O Jumper Setting (JP1)
4.2. External DIP Switch Settings (or Jumpers Settings)
4.3. Wiring Examples
J1
Orange
XE103-10
Name
I1 IN1
I2 IN2
I3 IN3
I4 IN4
I5 IN5
I6 IN6
I7 IN7
I8 IN8
H1 HSC1 / IN9
H2 HSC2 / IN10
H3 HSC3 / IN11
H4 HSC4 / IN12
A1 Thermistor 1
A2 Thermistor 2
0V Ground
J2
Black
XE103-10
Name
0V Ground
V+ V+ *
NC No Connect
Q12 OUT12
Q11 OUT11
Q10 OUT10
Q9 OUT9
Q8 OUT8
Q7 OUT7
Q6 OUT6
Q5 OUT5
Q4 OUT4
Q3 OUT3
Q2 OUT2 / PWM2
Q1 OUT1 / PWM1
V+* Supply for Sourcing Outputs
8
1
Pin MJ1 Pins MJ2 Pins
8
TXD OUT TXD OUT
7
RXD IN RXD IN
6
0 V Ground 0 V Ground
5
NC
No
Connect
NC
No
Connect
4
RTS OUT TX- OUT
3
CTS IN TX+ OUT
2
RX- /
TX-
IN /
OUT
RX- IN
1
RX+ /
TX+
IN /
OUT
RX+ IN
Note: The Cscape Module Setup configuration must match
the selected I/O (JP) jumper settings.
I1
0V
001XLE036
12-24VDC
I1
0V
Positive Logic In Negative Logic In
Positive Logic vs. Negative Logic Wiring
The XLE can be wired for Positive Logic inputs or
Negative Logic inputs.
Factory Use
(default – none)
MJ2 Termination
(default – none)
MJ1 Termination
(default – none)
001XLE037
As seen when looking at the top of the XLE unit. Refer to
Section 3 for the location of the External Jumpers.
Memory Slot:
Uses Removable Memory
for data logging, screen
captures, program loading and recipes.
Horner Part No.: HE-MC1
Serial Communications:
MJ1: (RS-232 / RS-485) Use for Cscape programming and
Application
-Defined Communications.
MJ2: (RS-232 / RS-485) Use for Application-Defined
Communications.
Location of I/O jumper (JP1
)
and wiring connectors
(J1 & J2).
Wiring Specifications
For I/O wiring (discrete), use the
following wire type or equ
ivalent:
Belden 9918, 18 AWG or larger.
For shielded Analog I/O wiring,
use the following wire type or
equivalent: Belden 8441, 18
AWG or larger.
For CAN wiring, use the
following wire type or equivalent:
Belden 3084, 24 AWG or larger.
Some XLes have jumpers to set RS-
485 port termination, tho
ugh most
use DIP Switches.
The External Jumpers or DIP
Switches are used for termination of
the RS-
485 ports. The XLE is
shipped un-terminated.
To terminate, select one of the
jumpers shipped with the product and
insert it based upon the option that is
desired or, select the switch and
configure based upon the option that
is desired.
Negative Logic
Positive Logic
JP1 Digital DC Inputs
Default
Q1
Q2
Q3
Q4
Q9
Q10
Q11
Q12
Q5
Q6
Q7
Q8
V+
0V
LOAD
LOAD
LOAD
LOAD
LOAD
LOAD
LOAD
LOAD
LOAD
LOAD
LOAD
LOAD
10 - 30VDC
Q13
001XLE024
LOAD
XE103-10 J2 Black
Positive Logic
Digital Out
Note: The wiring examples show
Positive Logic input wiring.
I1
I2
I3
I4
0V
I5
I6
I7
I8
H1
001XLE061
12-24VDC
A1
A2
H2
H3
H4
T
T
J1 J2
JP1
001XLE060
XE103-10 J1 Orange
Positive Logic
Digital In
001XLE037-R1
Factory Use
(default – none)
MJ2 Termination
(default – none)
MJ1 Ter
mination
(default – none)